Exide Higher KVA UPS Series II

Features
  • Wide Mains Input Voltage Range 100V - 290V
  • Controlled Output Voltage
  • Suitable for Mains Low Voltage Operation, 8 - 10 AMP Charging at 120V Mains Input
  • ASIC (Auto Sense Intelligent Control) technology for battery charging which automatically senses battery condition & adjusts the charging current accordingly
  • Soft Touch ON/OFF, Mode Selection & Charging Selection Switch
  • Smart In-built Protections - Overload, Short Circuit, AC Back Feed, Battery Low, Battery Over-Charge, Over Temperature etc.
  • Mains Overload through Resettable Switch
  • Primary Power Back up source for Industries, Corporate Offices and BPOs
  • Widely used in banks, multiplexes and shopping malls
  • Petrol Pumps, Fuel Dispensing Machines
  • Provides reliable back-up for Office Equipment such as Computers, Projectors, Printers, Scanners and Fax Machines etc.
  • All Motor based applications such as AC, Fire Pumps, Water Pumps, Compressors and other 3 Phase critical motorized equipment Water Coolers and Deep Refrigerators
  • Emergency and Transportable Power Systems
  • Gym /Health Equipment
Specifications
Product 5.2KVA 7.5KVA 10KVA 12KVA
Nominal Battery Voltage 96V 120V 180V 192V
Type Satic UPS Satic UPS Satic UPS Satic UPS
Output Wave Form Pure Sine Wave Pure Sine Wave Pure Sine Wave Pure Sine Wave
No Load Output Voltage 220V ± 7V AC 220V ± 7V AC 220V ± 7V AC 220V ± 7V AC
Output Frequency 50Hz ± 1Hz 50Hz ± 1Hz 50Hz ± 1Hz 50Hz ± 1Hz
No Load Battery Current ≤1.2Amp ≤1.2Amp ≤1.2Amp ≤1.2Amp
Full Load Output Current ± 1Amp 49Amp 56Amp 49Amp 59Amp
Total Harmonics Distortion (@ Linear Load) <3% <3% <3% <3%
Battery Low Pre-Alarm 10.8V ± 0.2V / Battery (12V DC of each battery) 10.8V ± 0.2V / Battery (12V DC of each battery) 10.8V ± 0.2V / Battery (12V DC of each battery) 10.8V ± 0.2V / Battery (12V DC of each battery)
Battery Low Cut-Off 10.5V ± 0.2V / Battery (12V DC of each battery) 10.5V ± 0.2V / Battery (12V DC of each battery) 10.5V ± 0.2V / Battery (12V DC of each battery) 10.5V ± 0.2V / Battery (12V DC of each battery)
Max. Charging Current (HC) 15A ± 1A 18A ± 1A 18A ± 1A 18A ± 1A
Max. Charging Current (NC) 12A ± 1A 14A ± 1A 14A ± 1A 14A ± 1A
Boost Charging Voltage 14.4V ± 0.2V / Battery (12V DC of each battery) 14.4V ± 0.2V / Battery (12V DC of each battery) 14.4V ± 0.2V / Battery (12V DC of each battery) 14.4V ± 0.2V / Battery (12V DC of each battery)
Float Charging Voltage 13.7V ± 0.2V / Battery (12V DC of each battery) 13.7V ± 0.2V / Battery (12V DC of each battery) 13.7V ± 0.2V / Battery (12V DC of each battery) 13.7V ± 0.2V / Battery (12V DC of each battery)
Input Voltage Range ± 10V{Normal Mode} 100V to 280V 100V to 280V 100V to 280V 100V to 280V
Changeover Time (Mains to Back-up){Normal Mode} < 40 ms < 40 ms < 40 ms < 40 ms
Changeover Time (Back-up to Mains){Normal Mode} < 10 ms < 10 ms < 10 ms < 10 ms
Input Voltage Range ± 10V{UPS Mode} 180V to 260V 180V to 260V 180V to 260V 180V to 260V
Changeover Time (Mains to Back-up){UPS Mode} < 10 ms < 10 ms < 10 ms < 10 ms
Protections Short Circuit Trip, Overload Trip, Battery Low & Over Charge Protection, Over Temperature Protection, AC Fuse Trip/ MCB Trip Protection, Phase Reverse Protection Short Circuit Trip, Overload Trip, Battery Low & Over Charge Protection, Over Temperature Protection, AC Fuse Trip/ MCB Trip Protection, Phase Reverse Protection Short Circuit Trip, Overload Trip, Battery Low & Over Charge Protection, Over Temperature Protection, AC Fuse Trip/ MCB Trip Protection, Phase Reverse Protection Short Circuit Trip, Overload Trip, Battery Low & Over Charge Protection, Over Temperature Protection, AC Fuse Trip/ MCB Trip Protection, Phase Reverse Protection
Display “ Tri Colour LCD Display which is showing: Mains Voltage, Battery Voltage, Applied Load in %, Battery Charging/ Charged, Battery Low/ Over Charge, Short Circuit, Overload, Over Temperature” “ Tri Colour LCD Display which is showing: Mains Voltage, Battery Voltage, Applied Load in %, Battery Charging/ Charged, Battery Low/ Over Charge, Short Circuit, Overload, Over Temperature” “ Tri Colour LCD Display which is showing: Mains Voltage, Battery Voltage, Applied Load in %, Battery Charging/ Charged, Battery Low/ Over Charge, Short Circuit, Overload, Over Temperature” “ Tri Colour LCD Display which is showing: Mains Voltage, Battery Voltage, Applied Load in %, Battery Charging/ Charged, Battery Low/ Over Charge, Short Circuit, Overload, Over Temperature”
Dimension LXWXH (in mm) 500X380X600 500X380X600 565X385X600 565X385X600
Net Weight (± 0.5Kg) 40.5Kg 52.1Kg 72Kg 72Kg
Gross Weight (± 1Kg) 42.7Kg 54.3Kg 87Kg 87Kg